SECTION 15832
AIR CURTAINS, INDUSTRIAL
NOTE ** This section is based on products manufactured by
Mars(R) Air Doors, at the following address:
NOTE ** 14716 South Broadway
NOTE ** Gardena CA 90248
NOTE ** Tel: (213) 770-1555
NOTE ** Tel: (800) 421-1266
NOTE ** Fax: (310) 324-3030
NOTE **
NOTE ** Mars Air Doors offers a complete line of Air
Curtains providing the benefits of temperature
control and environmental separation. Models are
offered in a commercial and industrial design and
can be configured with heat. Heated units include
gas, electric, steam and hot water coil models.
NOTE ** A typical installation is over a building's
exterior door or window opening. They provide
excellent protection at reducing a building's
heating and cooling costs when these exterior doors
need to be opened. At the same time, they repel
gusts of wind and minimize the entrance of
windborne dust, fumes, pollutants, and flies.
Additionally, they help to expedite the flow of
traffic from one work area to another or in and out
the building, by providing an unobstructive view of
the opening. This section covers the industrial
part of their product line: "Standard," "High
Velocity (HV)," "Extra Power (EP)," "Windguard
(BD)," "Extra High Velocity (EHV)," and "Extra High
H Velocity (EHH)" models. See their other Section
15831 for commercial models.
NOTE **
NOTE ** SECTION 15832 - AIR CURTAINS, INDUSTRIAL, Copyright
1998, The Architect's Catalog, Inc.
PART 1 GENERAL
1.1 SECTION INCLUDES
NOTE ** Select paragraphs below applicable to project.
A. Standard Models.
B. High Velocity Models.
C. Extra Power Models.
D. WindGuard Models.
E. Extra High Velocity Models.
F. Extra High H Velocity Models.
1.2 RELATED SECTIONS
NOTE ** Sections listed in the following paragraphs
represent those most likely to relate to this
section; coordinate with other sections, delete
those not relevant to this project, add others as
required.
A. Section 08110 - Steel Doors and Frames.
B. Section 08330 - Coiling Doors and Grilles.
C. Section 08500 - Windows.
D. Section 08580 - Pass Windows.
NOTE ** Retain one of the following two paragraphs; retain
second paragraph only if specifying heated unit.
E. Sections of Division 16 affecting, or affected by,
construction activities of this section.
F. Sections of Divisions 15 and 16 affecting, or affected
by, construction activities of this section.
1.3 SUBMITTALS
A. Submit under provisions of Section 01300.
B. Product Data: Manufacturer's descriptive literature for
products specified in this section; indicate options
specified.
NOTE ** Retain following paragraph only if specifying gas-
heated unit.
C. Shop Drawings: Indicate installation and connection
details.
D. Quality Assurance Submittals:
1. Certificates: Indicate compliance to Regulatory
Requirements specified in QUALITY ASSURANCE Article
of this section.
2. Manufacturer's instructions: Printed installation
instructions for each specified product.
E. Closeout Submittals:
1. Operation and maintenance data: Manufacturer's
printed instructions for operating and maintaining
air curtain components.
2. Warranty documents: Issued and executed by
manufacturer.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications: Minimum five years
documented experience producing respective products
specified in this Section.
NOTE ** Delete agency certifications below not required for
project.
B. Regulatory Requirements: Product compliance with the
following regulatory agencies:
1. Underwriters Laboratories listing.
2. National Electrical Code.
3. United States Food and Drug Administration.
4. United States Department of Agriculture.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Store products of this section in manufacturer's unopened
packaging until installation.
B. Maintain dry, heated storage area for products of this
section until installation of products.
1.6 WARRANTY
A. Manufacturer's Warranty: Supply manufacturer's standard
warranty against defects in product workmanship and
materials.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Acceptable Manufacturer: Mars Air Doors, 14716 South
Broadway, Gardena CA 90248; ASD. Tel: (213) 770-1555 or
(800) 421-1266; Fax: (310) 324-3030.
NOTE ** Delete one of the two following paragraphs;
coordinate with Division 01 requirements.
B. Requests for substitutions will be considered in
accordance with provisions of Section 01600.
C. Substitutions: Not permitted.
2.2 MANUFACTURED UNITS
NOTE ** Retain the following paragraph if specifying Mars
"Standard," "HV" (High Velocity), or "EP" (Extra
Power) Model units. "Standard" and "HV" models are
used over freezer and cooler doors to reduce
humidity and ice buildup, sealing in cold air and
saving energy. They are also used over
receiving/service entrances for both climate and
insect control.
NOTE **
NOTE ** "Standard," "HV," and "EP" models are used for
climate control and energy conservation; installed
inside of buildings with high ceilings, they bring
wasted hot air from the ceiling over the door
opening and to the floor level. This eases the
load on the heating system. These models are also
available heated with electric coils, gas, steam,
and hot water single or double row coils.
NOTE ** "Standard," "HV" (High Velocity), "EP" (Extra
Power), and "Windguard (BD)" models are all used
for the same reasons. The height of the door
dictates which model to use. All four of these
models are available in gas, electric, steam, or
hot water coil forms of heat. "Standard" and "HV"
models can also be used over cooler and freezer
doors. Units can be mounted either inside or
outside of the building. If using a heated model,
it must be mounted inside the building.
NOTE **
NOTE ** "EHV" and "EHH" models are for insect control only.
They are available as unheated models only. They
can be mounted either inside or outside of the
building.
A. Air Curtains:
NOTE ** Insert Model Number information in following
paragraph.
1. Acceptable Product: Mars Model Number ________.
2. Product Description: Self-contained electrically-
operated air curtain for mounting at head of
openings.
3. Housing:
NOTE ** Select one of the following two paragraphs
regarding welded metal or stainless; delete the
other.
a. Welded metal, with factory-drilled mounting holes
at each end for back wall mount.
b. Welded stainless steel, with factory-drilled
mounting holes at each end for back wall mount.
c. Air direction vanes, adjustable +/- 20 degrees
front to back.
NOTE ** Select the first paragraph below for "EHV" or "EHH"
models, the second paragraph below for "Windguard
(BD)" model, or the third paragraph below for
"Standard," "HV," or "EP" models. Delete those
paragraphs not applicable.
d. Fixed die-punched louver assembly.
e. Expanded metal inlet screen.
f. Adjustable inlet louver damper, reducing air
velocity up to 50 percent; field adjustable.
NOTE ** Delete the following paragraph if stainless steel
housing is specified above.
g. Color: Gray baked rust preventative,
electrostatic polyurethane powder coating.
NOTE ** Select the first paragraph below for "Windguard
(BD)" model, the second paragraph below for other
models. Velocity varies, depending on model
selected; check with manufacturer and insert
velocity required.
4. Blower Assembly: Belt-drive, double-width and double-
inlet squirrel cage blower wheels, producing minimum
velocity ____ feet per minute (____ m/sec) at 3 feet
(0.914 m) above floor with maximum opening height of
14 feet (4.267 m).
5. Blower Assembly: Direct-drive, double-width and
double-inlet squirrel cage blower wheels, producing
minimum velocity ____ feet per minute (____ m/sec) at
3 feet (0.914 m) above floor with maximum opening
height of 14 feet (4.267 m).
NOTE ** Delete three of the following four paragraphs;
insert requirements in remaining paragraph.
Consult manufacturer's product data for specific
model specifications.
6. Motors: Single ___ horsepower, maximum ____
revolutions per minute, ______-speed.
7. Motors: Two ___ horsepower, maximum ____ revolutions
per minute each, ______-speed.
8. Motors: Three ___ horsepower, maximum ____
revolutions per minute each, ______-speed.
9. Motors: Four 1/2 horsepower, maximum ____
revolutions per minute each, ______-speed.
NOTE ** Retain following paragraph if specifying unit with
optional door-activated microswitch.
10. Door-Activated Microswitch: Supply microswitch for
automatic on/off control; turns air curtain on when
door is opened and off when door is closed; field
installed.
NOTE ** Delete one of the following two paragraphs.
Plunger type is for doors with hinges (swing
doors), roller type for all other types of doors.
a. Type: Plunger.
b. Type: Roller.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
11. Operating Noise Level: __ decibels on A scale,
measured from interior, 10 feet from unit.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
12. Utility Requirements: ___ Volts AC, ______-phase,
___ Ampere(s).
NOTE ** Retain the following paragraph if specifying Mars
"EHV" (Extra High Velocity) or "EHH" (Extra High H
Velocity) Model units. These models are unheated.
They are primarily for insect and dust control for
use over loading dock door openings in meat, food,
and beverage processing plants, food storage, etc.
Weatherproof cover and adjustable mounting brackets
are included. Velocity controls are not provided.
B. Air Curtains:
NOTE ** Insert Model Number information in following
paragraph.
1. Acceptable Product: Mars Model Number E_______.
2. Product Description: Self-contained electrically-
operated air curtain for mounting at head of
openings.
3. Housing:
NOTE ** Delete one of the following two paragraphs.
a. Welded metal, with factory-drilled mounting holes
at each end for back wall mount.
b. Welded stainless steel, with factory-drilled
mounting holes at each end for back wall mount.
c. Removable inlet screen.
d. Air direction vanes, adjustable +/- 20 degrees
front to back.
NOTE ** Delete the following paragraph if stainless steel
housing is specified above.
e. Color: Gray baked rust preventative,
electrostatic polyurethane powder coating.
4. Blower Assembly: Direct-drive, double-width and
double-inlet squirrel cage stainless steel blower
wheels, producing minimum velocity 1600 feet per
minute at 3 feet above floor with maximum opening
height of 14 feet.
NOTE ** Delete two of the following three paragraphs.
Consult manufacturer's product data for specific
model specifications.
5. Motors: UL-listed, heavy duty, direct drive,
continuous duty type, totally enclosed with double-
sealed lifetime pre-lubricated ball bearings,
resilient mounted and protected by an automatic
thermal overload switch; on-off control switch.
6. Motors: UL-listed, two-speed, heavy duty, direct
drive, continuous duty type, totally enclosed with
double-sealed lifetime pre-lubricated ball bearings,
resilient mounted and protected by an automatic
thermal overload switch; on-off control switch.
7. Motors: UL-listed, explosion-proof, heavy duty,
direct drive, continuous duty type, totally enclosed
with double-sealed lifetime pre-lubricated ball
bearings, resilient mounted and protected by an
automatic thermal overload switch; on-off control
switch.
NOTE ** Insert motor requirements in paragraphs below.
Consult manufacturer's product data for specific
model specifications.
a. Quantity per Unit: ____________.
b. Horsepower: ______.
c. Revolutions per Minute (RPM): _________.
NOTE ** Retain following paragraph if specifying unit with
optional door-activated microswitch.
8. Door-Activated Microswitch: Supply microswitch for
automatic on/off control; turns air curtain on when
door is opened and off when door is closed; field
installed.
NOTE ** Delete one of the following two paragraphs.
Plunger type is for doors with hinges (swing
doors), roller type for all other types of doors.
a. Type: Plunger.
b. Type: Roller.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
9. Operating Noise Level: __ decibels on A scale,
measured from interior, 10 feet from unit.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
10. Utility Requirements: ___ Volts AC, ______-phase,
___ Ampere(s).
NOTE ** Retain the following paragraph if specifying Mars
"Windguard(R)" heavy-duty belt-drive units. These
models are used for oversize doorways up to 22 feet
high. They are also available with heat in steam,
hot water, electric, and indirect gas fired
designs.
NOTE **
NOTE ** Their purpose is to save on heating energy and
repel wind gusts up to 30 MPH in manufacturing
plants, food, beverage, and meat processing plants,
warehouses, hospitals, etc.
C. Heavy-Duty Belt-Drive Air Curtains:
NOTE ** Insert Model Number information in following
paragraph.
1. Acceptable Product: Mars WindGuard(tm) Model Number
BD-____-____-____.
2. Product Description: Self-contained electrically-
operated air curtain for mounting at head of
openings.
3. Housing:
NOTE ** Delete one of the following two paragraphs.
a. Welded metal, with factory-drilled mounting holes
at each end for overhead mount.
b. Welded stainless steel, with factory-drilled
mounting holes at each end for overhead mount.
c. Removable inlet screen.
d. No air directional vanes allowed. Nozzle
pivoting +/- 20 degrees front to back; internal
damper to reduce air flow up to 50 percent; field
adjustable
NOTE ** Delete the following paragraph if stainless steel
housing is specified above.
e. Color: Gray baked rust preventative,
electrostatic polyurethane powder coating.
4. Blower Wheels: Dynamically balanced, producing
minimum velocity 1600 feet per minute at 3 feet above
floor with maximum opening height of 14 feet.
NOTE ** Delete two of the following three paragraphs. The
first is for Model BD-14, the second for Model BD-
18, and the third for Model BD-22.
a. Average Velocity at Nozzle: 3400 feet per
minute.
b. Average Velocity at Nozzle: 4000 feet per
minute.
c. Average Velocity at Nozzle: 4700 feet per
minute.
5. Motor: Single ___ horsepower, maximum ____
revolutions per minute, ______-speed, with ______-
speed on/off control switch.
NOTE ** Retain following paragraph if specifying unit with
optional door-activated microswitch.
6. Door-Activated Microswitch: Supply microswitch for
automatic on/off control; turns air curtain on when
door is opened and off when door is closed; field
installed.
NOTE ** Delete one of the following two paragraphs.
Plunger type is for doors with hinges (swing
doors), roller type for all other types of doors.
a. Type: Plunger.
b. Type: Roller.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
7. Operating Noise Level: __ decibels on A scale,
measured from interior, 10 feet from unit.
NOTE ** Insert information into following paragraph;
consult manufacturer's product data for specific
model specifications.
8. Utility Requirements: ___ Volts AC, ______-phase,
___ Ampere(s).
NOTE ** Retain following paragraph if specifying unit for
uncovered exterior installation.
D. Fastening Devices: Types recommended in manufacturer's
printed installation instructions for indicated
substrates.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verification of Conditions: Required utilities are in
correct location and are of correct capacities for
specified products.
3.2 INSTALLATION
NOTE ** Retain the following two paragraphs only if
specifying gas-heated unit.
A. Install air curtain components in accordance with shop
drawings and manufacturer's printed installation
instructions.
B. Connection to utilities is specified in Sections of
Divisions 15 and 16.
NOTE ** Retain the following two paragraphs for all other
units.
C. Install air curtains in accordance with manufacturer's
printed installation instructions.
D. Connection to utilities is specified in Sections of
Division 16.
END OF SECTION